Skip to main content
CALC 12 · PRACTICALFREE

Wire Gauge Converter

INPUT

Range: 40 down to -3 AWG. Aught sizes are entered as zero and negatives: 0 = 1/0, -1 = 2/0, -2 = 3/0, -3 = 4/0

Sets the resistance basis and the ampacity lookup. Aluminum has recorded ampacity for a few sizes only; other sizes are refused, not estimated.

The column is the conductor insulation rating, not a termination limit. The 75°C copper column is the only one with a screening value for every AWG row.

COMMON AWG SIZES (USA)
CONVERSION RESULTS
AWG Size
14
Area (mm²)
2.08
Diameter (mm)
1.630
Resistance
8.286
Ω/km (copper, 20°C · basis in steps)
Primary-Verified Ampacity
20 A
copper, 75°C column · NFPA 70 (NEC) 2023 Table 310.16 · W0C sparse spot
Separate OCPD Coordination Required

small_conductor_240_4_D — The OCPD limits are primary-verified, but this conductor-conversion result does not select or coordinate a protection device.

Conversion Steps
  1. 01Input: AWG 14
  2. 02Cross-sectional area: 2.08 mm²
  3. 03Diameter: 1.63 mm
  4. 04Resistance: 8.286 Ω/km (copper, 20°C, tabulated AWG row)
  5. 05Primary-verified ampacity: 20 A (copper, 75°C column)
  6. 06Notice: Verified gate: apply the exact NEC 240.4(D) material/size OCPD limit after ambient-temperature and conductor-count corrections.
Formula
Tabulated AWG row (row values reproduce d = 0.127 × 92^((36−n)/39), A = π·d²/4)
QUICK REFERENCE
AWGmm²Ø (mm)Screening A (Cu 75°C)*
4/0107.2011.68230
3/085.0010.40200
2/067.409.27175
1/053.508.25150
142.407.35130
233.606.54115
421.205.1985
613.304.1165
88.373.2650
105.262.5935
123.312.0525
142.081.6320
161.311.2915
180.8231.0210

* Unverified copper 75°C screening references from the legacy dataset; they do not follow the material or column selected above. Select conductor ampacity from an applicable verified code pack.