Skip to main content
CALC 15 · PRACTICALPREVIEW

Breaker Sizing Calculator

Breaker Sizing · Advanced Preview
Available free during the correctness audit. Results remain screening-only unless the result itself states a stronger assurance level.
Access status
SAFETY CRITICAL CALCULATION

Improper breaker sizing can cause fires, equipment damage, or electrical shock. This calculator provides guidance only. Always consult local electrical codes and hire a licensed electrician for installations.

LOAD INFORMATION
A

Load current used by the selected screening path.

General branch-circuit screening; final rule source remains pending.
• Evidence: Primary numeric rule pending · screening only

If wire is already installed, check coordination

Actual conductor insulation only. It is the derate base; it is not the final termination limit.

Missing information conservatively blocks the next-size-up permission.

TERMINATION — NEC 110.14(C)
Circuit Rating Is Resolved First

The selected device rating is used as the circuit ampere rating for the termination rule. The wire check then verifies that fixed rating; it never guesses a ≤100 A or >100 A category.

A separate listed connector stacks an additional ceiling under 110.14(C)(2).

COMMON APPLICATIONS
Additional Input Required

Select the actual conductor insulation rating before checking wire coordination.

SIZING RESULTS

— AWAITING INPUT —

Enter load information to calculate

REFERENCE — NEC REQUIREMENTS
NEC 240.4(B)/(C) — Conductor Coordination
  • • Apply ambient and current-carrying-conductor factors first
  • • Next-size-up at or below 800 A requires all three recorded conditions
  • • Above 800 A, conductor ampacity must be at least the device rating
NEC 430.52(C)(1) — Motor SCGF Protection
  • • The motor/device matrix percentage is a maximum, not a minimum
  • • Default selection is the largest standard rating not exceeding that maximum
  • • Next-higher and starting increases are explicit, separately bounded exceptions
NEC 240.4(D) — Verified Small-Conductor Limits
  • • Material- and size-specific OCPD ceilings are enforced
  • • Limits are checked after applicable correction factors
  • • Table 310.16 ampacity remains distinct from the OCPD ceiling
Pending Application Sources
  • • Motor FLC table cells are pending; entered FLC stays screening-only
  • • HVAC 440.22 and welder 630.12 numeric rules remain pending
  • • Separate motor overload sizing is outside this SCGF result
Safety Notes

• Coordinate the selected device with corrected conductor ampacity and every applicable exception

• Always follow local electrical codes

• Use GFCI/AFCI where required by code

• Label all circuits at panel

• Hire licensed electrician for installations